STORAGE/DISPOSAL > Details
Oil storage installations should be sited on an impervious base
and surrounded by an oil-tight bund wall. The bunded area should
be large enough to contain at least 110% of the volume of the tank.
All the pipes and gauges should be enclosed within the bund, and
the vent pipe directed downwards into the bund. There should be
no drainage outlet in the wall and the installation should be protected
from vandalism. Further details can be found in:
Guidance
note PPG2 - Above Ground Oil Storage Tanks
Guidance
note PPG26 - Storage and handling of drums and intermediate bulk
containers (IBCs).
|